|
News
CROWN
Solutions, Inc. Technical Resource
Copper Removal from Cooling Tower Blowdowns
By: Chris Howell and Dave Christophersen
Discharge
of industrial non-contact cooling water (cooling tower
blowdown) to waterways has been, and continues to be,
performed worldwide. Several local, state, and federal
agencies administer the compliance programs necessary
to insure that the integrity of the public water ways
are maintained. Discharge limits for the constituents
in the discharged water continue to be lowered as better
detection limits are realized and technologies (physical
and chemical) advance to allow the reduction of the
various targeted constituents. In addition, greater
environmental pressure brought on by politics (local,
state, and federal) and technical requirements continue
to make discharge to a waterway more and more difficult.
Metals
in the discharged water have always been a concern and
are even more so today. Potable water standards are
now requiring much lower metals concentrations in the
water that we drink due to potential health risks and
therefore, the water discharged into surface water receiving
bodies must be as clean and sometimes, cleaner than
the water supplied to a facility as raw water or potable
drinking water to protect the water that we drink and
the ecosystem of the receiving water.
One
constituent that is being targeted on more regular basis
is copper in non-contact cooling water blowdown. Copper
occurs naturally in the makeup water used by industrial
facilities and also is introduced into the noncontact
cooling water (water used to cool a process without
coming in direct contact with that process) as a result
of corrosion byproducts from the industrial cooling
system components. Additionally, to minimize water usage
in a non-contact cooling system, the best acceptable
operations and engineering practice are to concentrate
the non-contact cooling water as much as possible by
minimizing blowdown to save on water and treatment chemical
costs. This practice elevates that concentration of
any impurities in the non-contact cooling water, and
in particular for this discussion, the copper concentration.
Treatment
Options
The treatment of industrial wastewaters is a common
practice. For some facilities, the wastewater treated
is primarily process wastewater from the production
of the end product manufactured at the facility and
the cooling tower blowdown may be a small portion of
the overall hydraulic or constituent loading of the
wastewater treatment plant. In other facilities, the
only “wastewater” is the cooling tower blowdown and
as such, the blowdown water is permitted for discharge
as “non-contact” cooling water. The discharged water
must meet the discharge limits set fourth in the National
Pollution Discharge Elimination System (NPDES) permit.
Manufacturing
facilities must meet compliance of the discharge permit
and periodically the permit parameters are re-evaluated
to insure compliance with local, state, and federal
requirements. If the compliance parameters for discharge
are changed, the facility may be required to install
a wastewater treatment strategy or wastewater treatment
plant (WWTP) to comply with the discharge limits.
The
options for metals removals from cooling tower blowdown
are:
- Change
the operation of the cooling system by reducing the
cycles of concentration and therefore reducing the
concentration of metals in the blowdown. This option
may not be allowed if the facility also has a hydraulic
and/or volumetric limit assigned to its NPDES. This
practice does not minimize natural resources as it
most likely will require more sourced makeup water
and a greater volume of water discharged to the environment.
- Install
a biological process that addresses the metals of
concern. These processes can be expensive and very
site-specific, and typically are less resistant to
upsets if a toxic component is introduced into the
system that affects the biology of the process.
- Install
a physical/chemical treatment process whereby the
metals are removed by adding treatment chemicals and
allowing the precipitated metals to be removed by
clarification and/or filtration. This type of process
can be further broken down as follows:
a. Traditional clarifiers and media filtration.
b. Electro coagulation and media filtration.
c. Filtration and ion exchange.
d. Membrane process utilizing microfiltration (MF),
ultrafiltration (UF), or reverse osmosis (RO). RO
would not typically be used for primary metals removal
because it is not tolerant to total suspended solids
(TSS) MF and UF would be used for TSS reduction followed
by RO for total dissolved solids (TDS) reduction if
wastewater reuse is desired.
Membrane
Technologies
Several membrane technologies are available to use for
industrial water preparation and wastewater recycling.
Typical membrane processes for solids removal include
microfiltration (MF) and ultrafiltration (UF). Major
designs include spiral wound, hollow fiber, and tubular.
Spiral membranes are relatively inexpensive and may
handle oils with the right membrane type as long as
total solids are low. Hollow fiber designs for UF and
MF are a popular configuration used today on surface
water and water reuse applications due to the ability
to handle relatively tough waters at a reasonable cost
and with a small footprint. One-inch tubular designs
can handle high solids and high levels of emulsified
oil concentrations. Smaller diameter 1/4” to 1/2” tubular
modular designs have lower capital costs than oneinch
tubes, but have more limitations than the oneinch tubes.
Pore
size can be used to define the type of membrane. Membrane
pore sizes are commonly expressed as nominal which means
that a membrane with a specified nominal pore size or
Molecular Weight Cutoff (MWCO) would be expected to
remove 90% of material of that size. The largest pores
in these membranes are likely larger than the nominal
pore size. Variations in pore size occur depending upon
the membrane type and manufacturer.
Microfiltration
ranges in size from approximately 0.05 mm to 1.0 mm.
Ultrafiltration
is a tighter membrane and is in the micron range of
approximately 0.005 - 0.1 mm. UF is typically expressed
in terms of molecular weight cutoff and ranges from
1,000 Daltons for a very tight UF membrane to approximately
500,000 Daltons for a very open UF membrane. By convention
for MWCO, it is assumed that the molecules are a polysaccharide
of that molecular weight; so actual filtration effectiveness
varies according to the specific chemistry of the molecule.
There is some overlap between the stated ranges for
MF and UF, so a membrane with a pore size that might
be considered to be a loose UF membrane might also be
considered to be a tight MF membrane depending on the
industry or manufacturer.
Membrane
Material
There are several different materials used to make membranes.
The membrane material, the actual chemistry, and how
the membrane is made vary by manufacturer. Some materials
that are used include polysulfone (PS), polyethersulfone
PES), polyacrylonitrile (PAN), polyvinylidene fluoride
(PVDF), polypropylene (PP), polytetrafluoroethylene
(PTFE), and ceramics.
The
membranes differ in their hydrophilic nature, tolerance
to oil, chlorine tolerance, applicable pH range, chemical
cleaning, strength, and cost.
PS
and PES are popular for suspended solids filtration
because the material is highly hydrophilic which allows
for high flux rate, has good cleanability, and has relatively
high resistance to organic fouling. It is also chlorine
tolerant to 200 PPM free chlorine or higher. They are
not good for oily water and can be brittle without proper
support.
PAN
also has high hydrophilicity and is a good choice for
oily water. It is relatively low cost, but is brittle
and has some chemical resistance restrictions.
PVDF
is not as hydrophyllic as PAN, but is also a good choice
for oil, stronger than PAN and more chemically resistant.
PP
is quite a bit less hydrophilic than PS, PES, PAN, and
PVDF and is also not tolerant of chlorine. It is low
cost and has high pH tolerance.
PTFE
is even less hydrophilic than PP.
Ceramics
offer high chemical and thermal tolerance, but generally
are expensive.
Spiral
Wound UF
Spiral wound UF membranes are made from flat sheet membranes
rolled into a spiral around a permeate core tube. These
membranes are commonly made of polysulfone. The membrane
modules looks similar to spiral wound RO modules and
are popularly housed in 8” diameter pressure vessels.
Feedwater, pressurized to about 20-100 psi, is fed to
one end of the spiral module. Feedwater travels across
the feed spacer and is forced through the membrane,
leaving behind suspended solids and particulates larger
than the membrane MWCO. Filtered water then travels
in a spiral to the filtrate core tube at the center
of the membrane module from where it can be transported
out of the membrane module as UF filtrate.
The
solids that are filtered out of the water by the membrane
are removed by means of a cross-flow velocity that continuously
scours the membrane surface. To maintain a cross-flow
velocity at the recommended levels, a proportion of
water that enters the system as feed leaves as concentrate.
To achieve high water recovery, roughly half of this
water is recycled to the feed stream, with a blowdown
stream used to remove solids from the system. Most spiral
wound systems cannot be physically backwashed; therefore,
over time, the membranes become fouled and the feed
pressure increases. At a certain feed pressure set point,
chemical clean-in-place (CIP) is performed. This can
occur as often as every few weeks to several months,
depending on the feedwater quality.
Hollow
Fiber UF and MF
Hollow fiber membrane systems for filtration have gained
wide acceptance in surface water treatment for potable
water production. For potable water applications, hollow
fiber membrane systems can guarantee removal of bacteria
and single cell organisms such as giardia and cryptosporidium
because the integrity of the membrane system can be
verified with integrity tests of the membranes in the
field. This is done by applying air pressure to the
membrane and monitoring for pressure loss and visually
looking for air bubbles. Extensive application of hollow
fiber UF and MF for potable water production has led
to the costs of this technology coming down to the point
where it is cost competitive with conventional water
treatment and spiral wound UF systems for RO pretreatment.
Industrial
applications include wastewater recycle after primary
or secondary treatment, metals removal, raw water clarification,
and RO pretreatment.
Hollow
fiber membranes used for filtration in industrial water
treatment may either be UF or MF membranes. The I.D.
of fibers is typically 0.5 mm (0.02 inch) – 1.2 mm (0.047
inch) diameter. Up to several thousand hollow fibers
are bundled into a membrane element. At either one or
both ends of the membrane element, the fibers are cast
in epoxy. Based upon membrane design, feedwater can
either be fed to the inside of the fibers, with filtrate
leaving from the outside of the fibers (inside-out),
or else feedwater can be directed to the outside of
the fibers with filtrate leaving from the inside of
the fibers (outside-in).
A
UF system can be set up with membrane modules arranged
in parallel or blocks as shown in Figure 1.
Hollow
Fiber Modes of Operation: Dead-end or Cross-flow
Dead-End Flow
For relatively cleaner waters such as front-end treatment,
hollow fiber systems are commonly operated in a dead-end
mode. All of the feedwater is directed across the membrane,
leaving the filtered particles behind on the membrane.
Particulates are removed from the membrane surface by
means of a physical backwash that forces the particulates
out of the membrane pores and away from the surface
of the membranes. The backwash may occur every 20 minutes
to every few hours, depending on the system and the
feedwater source. With the system operating in a dead-end
mode, operating pressures are generally low (commonly
around 10-25 psi), and there is no recirculation stream
that would require extra pumping power.
Over
time, the physical backwash will not remove some of
the membrane fouling. Most membrane systems allow the
feed pressure to gradually increase to around 20 - 30
psi and then perform a clean-inplace (CIP). CIP frequency
might vary from 7 days to several months. A good target
is every one to two months. Another approach is to use
a Chemically Enhanced Backwash (CEB), where, on a frequent
basis, chemicals are injected with the backwash water
to clean the membrane and maintain system performance
at low pressure without going off-line for a CIP. CEB
chemicals are usually sodium hypochlorite, caustic,
or acid. Much of the success of the hollow fiber filtration
process is establishing an effective backwash and CEB
program.
The
backwash and CEB strategy should minimize backwash water
losses while effectively returning the trans membrane
pressure (TMP) back to where it was at the start of
the previous cycle. A good target recovery rate calculated
as (filtrate volume/total volume including flushes)
× 100, is 92 – 95% with dead-end flow operation.
Flushing
and backwash commonly use filtrate water. Sometimes
it may be necessary to use other or better water sources
for this operation due to fouling that can occur when
the filtrate from the machine to be cleaned is not chemically
compatible with the CEB chemicals. The flushing and
backwash cycles allow the following options:
Cross-Flow
For higher solids waters or back-end treatment of wastewaters,
the membrane may be set up to operate in a cross-flow
mode. What could be a rapid buildup of solids at the
membrane surface is overcome by continuously removing
a small portion of the flow from the dirty feedwater
side of the membrane. This wastewater along with the
water lost in flushes and backwashes can lower the overall
recovery rate down to the 80 – 90% range. In both the
dead-end flow or the cross-flow, strategies can be incorporated
to capture, treat, and reapply the backwash water to
the front end of the membrane filtration process to
improve actual overall system recovery rate.
Forward
flush, backwash, and chemically enhanced backwash strategies
are similarly applied whether the system is operated
in the dead-end or cross-flow mode.
Figure
2: Dead-End vs. Cross-Flow Filtration
|
|
|
All
solids are left behind on the surface.
|
|
|
|
Solids
are removed with a side-stream bleed,
and surface fouling is reduced.
|
Table
1: Starting Point Guidelines
|
Water
Source
|
Hollow
Fiber Flux Rate (GFD)
|
|
City
water or pretreated surface water
|
70
– 90
|
|
Well
water
|
65 – 90
|
|
Raw
surface water
|
58
– 70
|
|
Sea
water
|
45
– 70
|
|
Cooling
tower blowdown and tertiary wastewater
|
32
– 50
|
|
Treated
industrial wastewater
|
20
– 55
|
The
performance and economics of filtration depend upon
the rate at which water flows through the membrane.
This is the flux rate and is expressed in gallons per
square foot of membrane surface area per day (GFD).
The system is set up to operate at a fixed flux rate
or filtrate flow rate by the use of a variable frequency
drive (VFD) on the supply or feed pump. Any accumulation
of retained material at the surface will reduce the
effective filtration rate and create the need for higher
supply pressure to maintain the set flux rate. Concentration
of solids at the surface occurs in a dynamic state but
its effect is similar to the filter cake build-up at
the separation surface in conventional filtration. The
TMP builds and the unit will go into the backwash cleaning
cycle. This is established by service cycle time. Excessive
TMP must be avoided to prevent damage to the membranes.
Actual
desirable flux rates depend upon the membrane manufacturer,
flow path, membrane material, water characteristics,
and water temperature. Some starting point guidelines
are shown in Table 1. The high-end flux rates are for
relatively clean feedwaters with turbidities of less
than 1 NTU or total suspended solids of less than 1
PPM. The low-end flux rates are for dirtier waters with
turbidities of 15 NTU or greater, and total suspended
solids of 20 PPM or greater.
Modified-Batch
for Hollow Fiber
For oily wastes or relatively dirty back-end waters,
the treatment may be set up in a modified-batch treatment.
With this method, a batch tank supplies the UF with
the cross-flow recycle stream returning to batch tank
along with new wastewater. A small concentrate stream
is wasted. The flow to the hollow fiber UF module is
changed back and forth from top-end feed to bottom-end
feed on regular cycles. As one end of the fibers foul,
the filtrate actually will provide an online backwash
of the fouled end because of the pressure differences
created within the module. After a period of time when
the TMP builds to a point, a CIP is performed.
Membrane
Life
The life expectancy of membranes depends upon many factors
including design flux rate, material, water characteristics,
operational design and implementation, and cleaning
frequency. As a rule, back-end treatment where wastewater
contains metals, organics, and oils will reduce the
life expectancy.
Table
2: Membrane Life Expectancy (Years)
|
Front-end
Water
|
Back-end
Water
|
|
Spiral wound |
3-6
|
2-3
|
| Hollow
Fiber |
3-8
|
1-4
|
| Tubular
|
3-8
|
2-5
|
Filtrate
Water Quality
Both UF and MF will remove suspended particles, algae,
and bacteria. UF will also remove viruses. Table 3 shows
the expected filtrate water quality from MF and UF systems
on raw water clarification and compares with multi-media
filtration. MF will generally provide a 15- minute silt
density index (SDI15) of less than 3 for surface or
well waters. UF commonly achieves an SDI15 below 2.
The lower SDI indicates a diminished potential for downstream
reverse osmosis fouling where an RO machine is part
of the treatment process. The removal of suspended solids
prevents fouling and blockage of the RO brine spacer.
Biofouling of RO membranes will be less likely with
the removal of bacteria by a MF or UF membrane process
used in front of the RO. Wastewaters containing oils
and surfactants and high TOC’s that are filtered by
MF or UF will commonly result in higher turbidities
and higher SDI’s than surface or well waters.
Table
3. Filtrate Water Quality on Surface or Well Waters
| Water
Quality |
Multimedia
|
MF
|
UF |
| Turbidity |
0.1
– 2 NTU |
<
0.1 NTU |
<
0.1 NTU |
| SDI15 |
3
– Filter Blinding |
<
3 |
<
2 |
Pilot
Testing
Every wastewater is unique to the facility and processes
used at the facility. Due to the high variability in
the wastewater, it is highly recommended that pilot
testing be conducted to verify the treatment process.
Pilot testing can be conducted as a lab scale bench
top test or as an onsite test with a pilot process that
can be scaled up for a full size application. This protects
the customer as well as the equipment vendor/contractor
by insuring confident results with little or no surprises
when the project is completed. The purpose for pilot
testing includes the following:
- Evaluate
the effectiveness and reliability of the technology.
- Determine
chemistry requirements, if any, of the UF feedwater.
- Determine
reliable flux rates.
- Determine
necessary backwash frequencies, flow rates, and durations.
- Determine
chemically enhanced backwash strategies (CEB).
- Develop
budgetary costs for full-scale operation.
- Test
CIP effectiveness.
There
are many challenges faced with this technology including
variations of influent water quality, temperature changes,
high TOC water, microbiological effects, and others.
Conducting a UF or MF pilot test requires monitoring
of several parameters and making effective adjustments
to determine if a full-scale system will be effective
and to determine how to design it properly.
The
pilot system has supervisory control and data acquisition
(SCADA) capability where operating data is automatically
acquired and stored. Manual data logging is also advisable
to backup the electronically stored data and to check
the sensor transmitters.
Case
Study
A world-class leader in the production of industrial
gases corporation owns and operates air separation units
(ASU’s) all over the world. Air separation requires
significant quantities of energy and as a result, heat
is generated in the process that must be removed. A
liquid oxygen ASU that supports a specialty gas pipeline
that extends through out the Gulf Coast in Texas was
faced with a reduction in the NPDES permitted concentration
of copper in their discharge. The facility utilizes
two large non-contact cooling systems to reject the
heat from the process to atmosphere by utilizing mechanical
drift cooling towers. The majority of the piping in
the cooling systems is carbon steel and the tube and
shell heat exchangers are constructed of carbons steel
shells with yellow metal (admiralty brass and copper)
tubes.
Makeup
water for the facility is sourced from the local river
water and canal water supply system. Makeup water is
untreated when it arrives at the boundary limit of the
facility. The makeup water is high in silt and natural
organics. An upflow, fluidized bed, continuous backwashing
sand filter is used to filter the makeup water to the
non-contact cooling system. Coagulation chemistry is
added upstream of the filter to improve the suspended
solids removal of the non-contact cooling system makeup.
The filtered makeup water is added to the cooling tower
sumps based on automatic level control and treatment
chemicals are added to the recirculated non-contact
cooling water to minimize corrosion, deposition, and
microbiological activity. Automatic blowdown of the
non-contact cooling water gravity drains to two small
retention ponds prior to discharge to the public water
way. Average blowdown volume is 100 gallons per minute
(GPM).
The
Texas Natural Resource Conservation Commission (TNRCC)
communicated a copper discharge limit of 17 PPB to the
facility. The owner of the facility had installed a
traditional physical/chemical copper removal system
(clarifier/media filtration) at another facility two
years prior. Although this system was effective at reducing
the copper concentrations to the desired discharge concentrations,
it requires a high degree of manpower and chemical addition
to operate. Two alternative technologies were compared
to the already proven physical/chemical technology to
see if a lower cost, better operating system could be
used. The two alternative technologies were selective
ion exchange and ultrafiltration (UF). Estimates for
installed ion exchange and ultrafiltration systems as
well as their projected operating costs were compared
against the known cost of the existing physical/chemical
system. The ultrafiltration system demonstrated the
lowest installed cost with the lowest operating costs.
A
small-scale pilot study was conducted on the ion exchange
strategy and a larger scale pilot study was conducted
utilizing the UF technology. The UF pilot was operated
for 240 hours at an average flowrate of 18.7 GPM. It
was originally thought that by adjusting the non-contact
cooling water blowdown to the minimum solubility of
copper (9.2 S.U.) that the UF membrane would remove
particulate copper and achieve the required copper removal.
The pilot demonstrated that this technique resulted
in premature fouling of the UF membrane due to carbonate
scaling of the membrane caused by exceeding the concentration
indices for calcium carbonate. Therefore, trithiocarbonate
(TTC) was dosed to the UF feedwater to help precipitate
the copper for removal by the UF membrane. This strategy
worked very well and allowed a membrane flux rate of
53 GFD to be realized.
The
UF membrane utilized for the pilot was a 500 square
foot, inside-out, polysulfone ultrafiltration membrane.
After
the successful pilot, a full-scale process was specified
and awarded as a design/build contract to CROWN Solutions,
Inc. The general scope of supply was as follows:
- A
prefabricated metal building to keep. all equipment
out of the weather: 30’ × 30’ × 12’ high. Adequate
lighting, heat, and ventilation for this building
included.
- An
8” slab with housekeeping pads for all equipment and
tanks: 30’ × 30’ × 8” thick. Civil Engineering will
be required to determine if this slab is adequate
for the ground built on. The Civil Engineering is
provided in this scope.
- All
interconnecting piping between Cooling Towers, existing
Equalization Tank, all equipment in the building,
and the drain to pond #1 located at the northeast
corner of the South Cooling Tower is included.
- All
electrical connections to included equipment, 480V
to 120V transformer, breakers and electrical distribution
equipment, building lights, heat, and vents is included.
- All
associated equipment for the project to include 2
(two) 70 GPM UF Filters, to operate individually or
in parallel, all required pumps, clarifier, tanks,
chemical feed equipment, control package, softener
and CIP system.
- Project
Management and Engineering to supervise the entire
construction effort.
The
system had the requirements for inlet water quality
and was guaranteed to provide the indicated performance.
(See Table 4.)
Overall
recovery of the process was optimized by directing the
backwash from the UF system to a storage tank to allow
for additional processing of the backwash through an
inclined plate clarifier. The clarified effluent from
the inclined plate clarifier was directed back to the
UF equalization tank for additional processing by the
UF machines. Clarifier sludge was be collected in a
filter press and disposed of by the Owner.
Had
the economics warranted, a RO process could have been
placed downstream of the UF system and the cooling tower
blowdown water could have been reclaimed back as to
the cooling tower as cooling tower makeup. The process
flow for the system is shown in Figure 4.
Table
4: System Requirements

|
|
|
Figure
3: Pilot Hollow Fiber UF System and Pilot Reverse
Osmosis System
|
The
case study system has been operational since late 2004.
Hurricane Rita caused damage to the facility, which
caused it to be shut down for several months while repairs
were made. The UF system did not sustain any physical
damage as a result of the hurricane and was operational
when the facility was placed back in service.
In
conclusion, MF and UF systems can be very effective
economical processes to meet cooling discharge compliance
requirements and provide better results than other treatment
methods.
About
the Authors
Chris
Howell is the Sales Manager and Director of New
Business Development, Design/Build Division for CROWN
Solutions, Inc. Mr. Howell previously was a senior project
engineer and project manager for CROWN. He joined CROWN
Solutions in 1993. Prior to that, he was a senior station
chemist at the Davis Besse Nuclear Power station and
was in the Naval Nuclear Power Program. Mr. Howell holds
a university degree in nuclear engineering technology.
Dave
Christophersen is a partner in CROWN Solutions,
Inc. and is their Technical Support Manager. Mr. Christophersen
has been involved in the water treatment industry since
1977 where he worked at Olin Corporation until 1981.
He then worked for Betz until 1986 before joining CROWN.
Mr. Christophersen is a member of the Association of
Water Technologies, the Cooling Technology Institute
and the National Association of Corrosion Engineers.
Dave has written papers for AWT, NACE, IWC, ULTRAPURE
WATER Magazine, and has presented at several conferences.
|
|
|
Figure
5: 2 × 70 GPM Ultrafiltration Skid and Control
Panel
|
|
|
|
Figure
6: WWTP Under Construction
|
|