|
News
CROWN
Solutions, Inc. Technical Resource
Introduction
Jim Marten - Vice President/Marketing Manager
In
this month's edition of the CROWN Technical Resource,
we discuss the use of automation for boiler blowdown
control.
Boiler
blowdown control is a critical function to the operation
of a boiler system. Many boiler systems do not have
automation schemes for blowdown control.
Boiler
blowdown automation can reduce fuel, water, sewer, chemical,
and manpower costs. In the current energy climate, the
justification for the equipment required to automate
boiler blowdown is even greater. Automated boiler blowdown
control should be an operating function of every industrial
boiler system.
If
there is anything that we can do for you, or if you
have any questions of comments regarding CROWN's service
to your organization, please contact me directly.
Regards,
James
N. Marten
Vice President/Marketing Manager
Phone: 1-800-875-4075 (x) 211
Fax: (937) 898-7360
jmarten@crownsolutions.com

CROWN
Equipment Division Two-Station Blowdown Controller
Saving Money with Automated Boiler Blowdown Control
By James McDonald, PE, CWT
The
primary and most efficient way to control boiler conductivity
is with continuous or surface blowdown from the steam
drum. This is the point of the highest dissolved solids
in the boiler and ensures a maximum of dissolved solids
are removed with a minimal loss of water and heat from
the boiler. Continuous blowdown is controlled in one
of two ways: manually or automatically.
Manually
Blowing Down
How tightly the conductivity can be controlled with
manually controlled blowdown will depend upon:
- How
frequently the boiler conductivity is tested.
- How
sensitive the blowdown valves are.
- How
attentive the operators are to the boiler.
- How
dynamic the steam load is.
If
the average boiler conductivity is too low, too much
makeup water will be used, too much blowdown will be
generated, too much fuel will be consumed, and too much
treatment chemical will be used.
On
the flip side, if the average boiler conductivity is
too high, the make water usage and blowdown rate may
be reduced, but the risk of carryover, scale, deposits,
sludge, and corrosion are increased.
Figure
1 shows an example of what manually controlling boiler
conductivity may look like. The boiler conductivity
setpoint is 4,000 mmhos, but the average conductivity
being maintained is only 3,755 mmhos. The standard deviation
is 336 mmhos.
Those
familiar with the Six Sigma management concept know
that to achieve process improvement, the average must
be moved in a positive direction (closer to the setpoint)
and the standard deviation must be reduced. Automating
boiler blowdown can achieve both of these goals.
Automatic
Boiler Blowdown
With automatic blowdown, tighter control of the boiler
conductivity can be achieved. Figure 2 shows a continuation
of the previous example with automatic blowdown control.
With the controller, the average conductivity is now
4,000 mmhos, and the standard deviation is just 200
mmhos.
How
They Work
Automatic boiler blowdown controllers are programmed
to take a cooled sample of each boiler on a timed basis.
Every so many minutes, the cooled boiler water conductivity
is checked and compared to the setpoint. If more than
one boiler is controlled with the controller, it will
cycle through each boiler with enough pre-flush time
to ensure an accurate sample of each boiler. If the
conductivity is too high, the boiler surface blowdown
valve is opened. The next time the boiler is sampled
(a.k.a., sample frequency), if the boiler conductivity
is still too high, it leaves the blowdown valve open.
If the conductivity is below the setpoint, it closes
the blowdown valve. This is a pretty simple, yet very
effective, process.
The
secret to a good automatic blowdown controller is a
cooled sample. Cooling the boiler water prior to reading
the conductivity improves reading consistency, reliability
and increases probe life.
Level
of Control
The level of control achievable with a boiler blowdown
controller will depend upon the boiler system, but a
survey of CROWN associates indicates that a deadband
of 200-400 mmhos is achievable on most systems. With
fine tuning, a deadband of 100 mmhos is not impossible.
Having
a well-kept boiler conductivity also makes controlling
chemicals much easier. When controlling internal treatment
chemicals, the first thing to consider is the conductivity.
If the conductivity is too high, then the phosphate,
EDTA, etc. will probably be high. If the conductivity
is too low, then these same treatment chemicals should
be low too. If the boiler operators don’t take this
into consideration at all times, they can end up “chasing
their tails” to control boiler chemicals. They may turn
down the chemical pump setting and increase blowdown
at the same or vice versa. Either way, the chemical
level will swing much further than expected.


Justification
Automatic boiler blowdown controllers can be justified
in several ways:
- Plot
the past conductivity data to visually show the level
of control and determine the average conductivity
and standard deviation.
- If
the average conductivity is too low, calculate the
amount of water, fuel, sewer, pretreatment, and chemicals
savings that would be realized if the average conductivity
was at setpoint.
CROWN
Associates have the tools available to assist in these
calculations.
|