|
News
CROWN
Solutions, Inc. Technical Resource
Introduction
Jim Marten - Vice President/Marketing Manager
An
unintended consequence of operating a cooling tower
is the fact that they are air scrubbers as well. Dust,
pollen, cotton wood fibers, and dirt are all pulled
into cooling towers as they operate and scrubbed from
the air with water. These solids can then settle out
in the cooling tower system and lead to under deposit
corrosion, blockages, and increased microbiological
activity.
Sidestream
filtration is a tried and proven method for removing
these solids from cooling tower systems. This article
discusses one case example and recommendations for sidestream
filtration.
If
you have any questions, or if there is anything that
we can do for you, please contact me directly.
James
N. Marten
Vice President/Marketing Manager
Phone: 1-800-875-4075 (x) 211
Fax: (937) 898-7360
jmarten@crownsolutions.com

Cooling Tower Sidestream Filtration
By Jeff Eldridge, CWT
The
ramps and taxiways in front of the main hangars in at
an Air Force Base were replaced. Approximately 250,000
square feet of concrete was broken into large pieces
and crushed to make gravel. The crushed concrete gravel
was used for fill and as an ingredient in the concrete
poured for the project. The construction project took
about four months during the summer.
Adjacent
to the construction project is a building that contains
offices and laboratories. The air conditioning for the
facility is produced by a 500-ton cooling tower system.
The cooling tower is located at ground level next to
the building.
|
Information:
- 500-ton
Marley cross flow cooling tower
- Galvanized
steel and PVC construction
- Concrete
sump, 8. x 12. x 10.
- 2
vertical pumps, 1,500 gpm each, located
in the sump, only one runs at a time
- 2
each 500-ton Trane centrifugal chillers
- System
volume: 6,500 gallons
|
|
The
cooling tower operated in an extremely dusty environment
all summer. During the operating season, the strainers
on the circulating system had to be cleaned multiple
times. The mechanics said that the system was dirty,
and they had operating problems all season. When the
system was drained for winter, the sump was ½ full of
sludge. The chillers contained sludge in low flow areas
and strainers were partially plugged with sludge. It
took two mechanics two days labor to clean the sludge
out of the sump.
What
happened to cause this problem? Cooling towers are air
washers. As such they remove airborne microorganisms,
seeds, dust, and etc. from the air flowing through the
cooling tower. The rock crusher for the construction
project was located about 50 yards up wind from the
tower. The dust from the rock crusher was pulled into
the tower and washed out of the air. The dust accumulated
and produced the sludge found in the system. Traditional
chemical treatment and blowdown could not remove the
debris. The concrete sump became the low flow area where
the bulk of the debris settled out of the water.
What
can be done to improve operations and minimize problems
caused by airborne materials? Moving the cooling tower
or the construction project was not an option. Other
possibilities are:
- Install
filter media on the intake louvers of the cooling
tower.
- Install
a sidestream filter on the circulating cooling tower
water.
Filter
media on the intake louvers would remove the dust before
it entered the cooling tower. The media comes in rolls
and requires a mounting apparatus. The mechanics would
need to replace the filter media periodically. This
method has been used but is labor intensive and requires
a large quantity of filter media.
A
sidestream filter would be an effective device to remove
debris from circulating cooling tower water. A bag filter,
sand filter or multimedia filter could be installed
on the cooling tower system to remove debris and prevent
problems associated with suspended solids accumulating
in low flow areas of the system. A bag filter would
be more labor intensive than a sand filter. For the
cooling tower system at this particular building, a
sand filter would be the best choice.
Both
a bag filter and sand filter could be used. The decision
to choose one over another is based upon site-specific
factors:
- Space
- Manpower
availability
- Backwash
water availability
- Initial
capital cost
- Particle
size analysis
Filters
are normally sized based on a percentage of the recirculation
rate. The general rule would be 5-10% of the recirculation
rate. The type of suspended solid and its concentration,
as well as the filtration efficiency needed determines
the percentage of flow required. The CROWN Equipment
Division specification for steel multimedia filters
lists three grades of water quality. The grades of water
quality are Superior, High, and Utility. Each is based
upon water flow rates through the filter.
Utilizing
recirculation rate the cooling tower system would need
a 75-150 gpm filter. This filter could produce all three
grades of water quality depending upon the size (dimensions
and cubic feet of media) of the filter.
Filters
can also be sized based upon the system volume. The
filter is typically sized to turn over the system volume
8 times in a 24-hour period. To determine filter flow
rate multiply the system volume by 8 and divide by 1,440
minutes to get the gpm capacity of the filter.
Utilizing
system volume, the cooling tower system would need a
36-gpm filter. This filter would produce all three grades
of water quality depending upon the size (dimensions
and cubic feet of media) of the filter.
For
the cooling tower, the system volume was determined
by the salt test. A filter based upon system volume
would be smaller and thus have a lower initial capital
cost.
The
filtered water should be returned to the cooling tower
in the areas of lowest flow. Many times the filtered
water is piped into a header system that discharges
the water around the sump to sweep the debris into the
suction of the filter.
Be
careful if you choose to install a filter that robs
flow from the equipment to be cooled. Many cooling tower
systems are undersized and diverting flow could cause
problems. If the system is of marginal capacity for
flow, you may need a separate pump to supply the filtration
equipment.
A
multimedia or sand filter would have helped prevent
the accumulation of sludge in the cooling tower system
at this building.
|