|
News
CROWN
Solutions, Inc. Technical Resource
Boiler & Cooling Tower Control Basics
By James McDonald, PE, CWT
For
those of us who have been around boilers and cooling
towers for years now, it can be easy to forget how we
may have struggled when we first learned about controlling
the chemistry of boilers and cooling towers. After running
all the chemical tests, where do you start when the
phosphate is too high, conductivity too low, sulfite
nonexistent, and molybdate off the charts? Even better,
how would you explain this decision process to a new
operator?
Cycles
of Concentration
The first place you always start is cycles of concentration
(cycles). You may measure cycles by measuring conductivity
or chlorides. If everything else is running normally,
when the cycles are too high, everything else should
be proportionally too high. When the cycles are too
low, everything else should be proportionally too low.
When the cycles are brought back under control, the
other parameters should come back within range too.
Example
We wish to run a boiler at 2,000 µmhos, 45 ppm phosphate,
and 40 ppm sulfite; however, the latest tests show 1,300
µmhos, 29 ppm phosphate, and 26 ppm sulfite. The conductivity
is 35% lower than what it should be. Doing the math
((45-29)/45=35%), we see that the phosphate and sulfite
are also 35% too low. By reducing boiler blowdown and
bringing the conductivity back within control, the phosphate
and sulfite should be within their control range too.
Beyond
Cycles
Whether we’re talking about boilers or cooling towers,
we know if we reduce blowdown, cycles will increase,
and if we increase blowdown, cycles will decrease. We
also know the other constituents in the water (phosphate,
sulfite, molybdate, etc.) will change in the same direction
as the cycles change. The only time this rule will not
hold true is when there are other variables at work.
What
if you’ve accounted for the change in cycles but the
other constituents are still out of range? This requires
you to think a little harder.
Chemical
Overfeed & Underfeed
Maybe the chemicals are simply being overfed or underfed.
This is easily remedied by turning the feed pumps up
or down or changing the amount added to the day tank
for a boiler.
Simply
changing the feed rate sounds easy, doesn’t it? Not
so fast! Unless you understand the chemistry, you may
not get the results you expect. You may grossly over
estimate the change required.
Remember
that a lot of the chemistry applied has a “demand” and
a “residual” component to the chemistry. For example,
when feeding bleach to a cooling tower, you first must
meet the free chlorine “demand” before you establish
a “residual.” If you currently test 0.2 ppm free chlorine
residual but want 0.4 ppm, you may be tempted to double
the setting on the bleach pump. By doing this, you have
completely ignored that the system had a 60 ppm free
chlorine “demand” as well. Currently the total chlorine
dosage was 60.2 ppm (60 + 0.2 ppm). If you double the
pump setting, the new dosage will be 120.4 pm (2 * 60.2).
The new free chlorine residual will be 60.4 ppm (120.4
– 60 ppm)! Somehow, I don’t think this is what you expected.
This
same “demand” versus “residual” logic applies to chelants
(EDTA), phosphate, sulfite and other oxygen scavengers,
etc. The lesson here is to know your chemistry.
Beyond
Overfeed/Underfeed
There are other factors that can lead to a constituent
being out of range besides a chemical overfeed or underfeed,
and these must be considered before a change to the
feed rate is made. Perhaps a piece of equipment isn’t
operating properly or process contamination is occurring.
By knowing the system, equipment, and what each individual
chemical constituent does, it shouldn’t take you long
to figure out the cause and proper corrective action.
Instead of going into a general vague discussion of
this subtopic, I think it will be more useful to describe
several examples. Each of these examples assume that
cycles have been corrected or considered already.
Sulfite
Level Too Low
Sulfite is added to a boiler system to remove oxygen
from the water. When a deaerator is used, sulfite removes
what oxygen is left after the deaerator mechanically
scrubs the oxygen from the water. If the deaerator is
not functioning properly, then more oxygen will be left
in the water, and more sulfite will be required to remove
it. This easily explains why sulfite levels may be too
low or why more sulfite than usual has to be fed to
maintain levels. If the deaerator temperature is too
low (typically <220°F) or if the deaerator isn’t being
vented enough (15-33 inches of actively moving plume),
then not enough oxygen is being mechanically scrubbed
from the water and the sulfite “demand” increases. Another
source for the problem may be a mechanical failure in
the deaerator itself such as bad spray nozzles or jumbled
trays.
Chelant
Too Low
The purpose of the chelant (typically EDTA) in a system
is to combine with metal ions to keep them soluble so
they won’t form scale in a boiler. Any metal ions that
are in a boiler such as calcium, magnesium, iron, etc.
make up the “demand.” The free chelant residual you
wish to carry is the “residual.” If anything happens
to increase the chelant demand such as hardness leaking
past a softener or corrosion byproducts coming back
in the condensate, then the chelant residual is going
to drop accordingly.
Phosphate
Too Low
Phosphate, in a low pressure boiler system, is used
to precipitate hardness into a loose sludge that can
easily be blown down. If more hardness is introduced
to the system than usual due to malfunctioning pretreatment
equipment or hard water leakage into the condensate
system, then the phosphate demand increases and less
may show up in the phosphate test. I say “may show up”
because the phosphate test can indicate both the combined
and uncombined phosphate, and the result will only be
lower if appreciable amounts of phosphate sludge are
blown down from the boiler. Running filtered and unfiltered
phosphate tests on the boiler water will give a better
understanding of what is happening.
Constituent
Levels Too High
For the same but opposite reasons in the examples above,
constituent levels may be too high. Perhaps a heat exchanger
has been fixed and hardness is no longer contaminating
the condensate. Then chelant or phosphate levels may
suddenly be higher. Perhaps oil is no longer leaking
into the cooling tower, so the chlorine demand has gone
down, resulting in higher free residuals. Perhaps the
deaerator is finally venting properly and sulfite demand
has dropped, resulting in higher residuals.
Other
Causes
Never rule out malfunctioning chemical feed pumps and
chemical control equipment. I have seen chemical feed
pumps behave erratically because of shorts in their
control switches. I’ve seen cooling towers overfeed/underfeed
chemicals or blowdown improperly because the sample
line with the conductivity probe had its water flow
turned off. This resulted in the controller thinking
the cooling tower conductivity was higher or lower than
it actually was and feeding chemicals and blowing down
accordingly. I’ve seen chemical pump settings changed,
but no one owns up to making the change. This is why
it is good to log the chemical pump settings. I’ve seen
softener multiport valves leak through so the sample
you tested showed hardness while the unit was actually
making soft water. I’ve seen operators change pump settings
by decreasing the speed and increasing the stroke, not
realizing that they may have actually increased the
chemical feed instead. Changes in makeup water characteristics
can also affect system control (such as phosphate added
to city water for corrosion control by the city or hardness
levels changing).
Test
Interferences
Don’t rule out test interferences either. Knowing your
tests, how they should look, and what interferes with
their results is invaluable. Keep a running inventory
of chemical usage so you can compare test results to
actual usage rates.
Conclusions
There is a lot to consider when it comes to process
control and water systems. The more you do it, the more
second nature it becomes. Whether you are new to the
water field or an old timer, just remember to start
with the cycles (conductivity or chlorides) and work
you way up from there.
For
more information about the control specifics of your
water system, please contact your water management professional.
|