A
midwestern industrial plant had a problem. The plant
had a cooling tower that supplies cooling water to
air compressors, oil coolers, air dryers, and various
process equipment. The local city water and sewer
rates were increasing significantly and their molybdate-based
chemical treatment costs were skyrocketing as molybdate
costs had risen nearly 1,000% lately! In an effort
to cut operating costs, the plant looked for ways
to decrease their cooling tower makeup water, sewer,
and chemical requirements. Various
ideas were investigated such as:
- Improved
blowdown controller
- Fixing
leaks
- Acid
feed
- Soft
water makeup
- Blended
city/soft water makeup
- Water
treatment chemistry
-
Recycled
wastewater
Cooling
Tower Basics
Once-through cooling allows water to be used once
for cooling before it is discharged. Cooling towers
allow the same water to be used repeatedly for cooling
before it is discharged. What limits the number of
times the same water can be used is solubility of
various dissolved ions in the water. When concentrated
high enough, some dissolved ions will become insoluble
and start forming scale in the system. Typically,
calcium carbonate is the first species to cause scale.
For example, for a cooling tower system with a temperature
change of 10°F and running at 3 cycles of concentration
(cycles), one pound of makeup water gets used an average
of 145 times before it is discharged via blowdown.
That is much more efficient that 1 pound of water
only being used once in once-through cooling.
As
a yearly average, approximately 75% of the cooling
action in a cooling tower results from evaporation,
while 25% is transferred to the air through sensible
heat.
Case
Study
The original operating characteristics for the midwestern
industrial plant being discussed are listed in Table
1. Calcium carbonate scaling potential was the limiting
factor for how many cycles the cooling tower could
run.
Improved
Blowdown Controller
It was known that the cooling tower blowdown controller
was old and unreliable. Sometimes it would blow the
system down too much and other times not enough. Blowing
down too much wastes water and chemical. Not blowing
down enough could lead to scale formation in the cooling
tower.
Table
1: Original Cooling Tower Operating Characteristics

A
review of the system parameters in Table 1 shows the
system was only running at an Langelier Saturation
Index (LSI) of 1.8 and cycles of 3. The LSI is a measure
of calcium carbonate scale forming tendencies. The
higher and more positive the number, the more likely
calcium carbonate scale will form. Typical cooling
tower chemistries can control an LSI of 2.5. This
means the cooling tower could really run at 4.6 cycles
if the controller would control the conductivity properly.
The plant replaced the blowdown controller with a
new one. Even though the controller was working correctly,
the cycles only increased to 3.6. There must have
been a leak in the system wasting more water than
what was required for blowdown to maintain the cooling
tower at 4.6 cycles.
Fixing
Leaks
Blowdown is used to control the cycles of concentration
(or conductivity) of a cooling tower system. If a
leak is bigger than the required blowdown, it will
be impossible to maintain the proper cycles or conductivity.
The plant traced the cooling piping and found a valve
had been opened to the drain. When the valve was closed,
the cooling tower was able to be controlled at 4.6
cycles.
Acid
Feed
Lowering the pH of the system would increase the solubility
of the calcium carbonate and allow more cycles to
be run. Because of safety considerations, the plant
decided not to use acid feed.
Water
Treatment Chemistry
For various reasons, molybdate prices are going through
the roof. Chemical treatment products that contain
molybdate cost more as a result. There are numerous
non-molybdate cooling tower products that can be used.
Also, while in the past the highest LSI that could
be run was 2.5, new polymers on the market allow the
system to run at an LSI of 3.0. This would allow the
cooling tower to run at 6.4 cycles and save water,
sewer and chemicals.
Soft
Water Makeup
One way to avoid calcium carbonate scale is to remove
the calcium itself. Using a water softener to remove
the calcium and magnesium from the makeup water would
allow the system to run at much higher cycles. Once
the calcium is removed, the limiting factor becomes
the chlorides in the water (<3,000 ppm). Running the
calculations shows that 56.6 cycles of concentration
could theoretically be obtained! However, cooling
towers are never tight enough to run anywhere near
this level due to drift, windage, short circuiting,
and process leaks. Typically the highest practical
cycles of concentration obtained in a cooling tower
is 12 to 17 cycles.
Table
2: Cooling Tower Savings Comparison

Notes:
Each cost cutting measure is independent and not additive.
1. Assumes new blowdown controller installed.
2. Assumes new blowdown controller installed and leaks
fixed.
3. 50% soft/city water blend
4. RO concentrated supplies 25% of the total makeup.
Blended
City/Soft Water Makeup
There are operating costs associated with running
a water softener such as salt costs and regeneration
water costs. Perhaps a blend of soft water and city
water would allow the cycles to be increased enough
to save money but not be offset by the softener operational
costs. The plant compared the savings of 100% soft
water to a blend and found the 100% soft water program
to show more savings.
Recycled
Wastewater
Some wastewaters are of sufficiently high quality
to use as cooling tower makeup without any extra treatment.
Reverse osmosis (RO) concentrate can be a good source
of makeup if the water is softened prior to the RO.
The plant did have an RO nearby for boiler makeup
and process water. The concentrate from the RO was
going to the drain, but could easily be collected
in a tank to use as cooling tower makeup. RO concentrate
is typically high in alkalinity, so it is important
to either degasify the water or only mix it with soft
water to avoid scale.
Conclusions
Table 2 shows the results of the midwestern industrial
plant’s evaluation of their options to save money
in the operation of their cooling tower. As you can
see in this particular case study, the savings are
significant. The plant ended up installing a new blowdown
controller, fixing the leak, and using 100% soft water
makeup with a non-molybdate chemical treatment for
a total savings of $146,980/year. They plan to use
RO reject in the future for an addition $9,500/year
savings.
Savings
will vary depending system parameters and makeup water
quality. Your Water Management Specialist should be
able to calculate any savings for you.